Explainer
Why WinCC Sm@rtAccess needs a WinCC flexible runtime
Short answer
Sm@rtAccess is an option of the WinCC flexible runtime, not of ProTool: a panel executing a downloaded ProTool application cannot offer it, no matter what is installed on the engineering PC. Remote access requires migrating the project to WinCC flexible on a supported panel with the option licensed, or moving to a PC runtime.

On this page
No: WinCC Sm@rtAccess cannot run on a panel executing a ProTool application, because the hard requirement is a WinCC flexible-family runtime on the device. Sm@rtAccess is compiled into that runtime image, so the fix for you is to migrate the project to a supported panel with the option licensed, or to move the application to a PC runtime.
The answer: it is a runtime option #
No. WinCC Sm@rtAccess cannot be used with a ProTool application running on an HMI panel. Sm@rtAccess is an option of the WinCC flexible runtime: it enables client or server access from one panel to another, and that capability is compiled into the runtime image that executes on the panel. A panel running a downloaded ProTool application has no such service inside it, so there is nothing for a remote client to attach to.
The distinction that decides this is engineering tool versus runtime. The engineering tool (ProTool, or WinCC flexible) runs on your PC and builds the project. The runtime is the software image executing on the panel itself. Installing WinCC flexible on the workstation changes nothing on a panel whose runtime is a ProTool image. Treat remote access as a runtime capability, never as a connection you can bolt onto any panel application.
The decision tree is therefore short: identify the panel and its runtime, check whether that panel is documented as suitable for WinCC flexible and the Sm@rt options, and then either migrate the project or replace the panel. The sections below take those steps in order.
Identify what is actually executing on the panel #
Record the exact HMI model, the installed system software and the runtime identity, plus the engineering software that produced the current project. Read the device identification and system information screens on the panel itself, and compare them with the project's configured target. Do not infer the runtime from what is installed on the engineering PC.
Before changing any software, preserve an editable backup of the existing project and record the current communication configuration. That archive is your way back if the migration fails, and the migration targets described in how to migrate a ProTool HMI project to a new touch panel all expect it as the starting point. If only a compiled application can be recovered from the panel, read why a replacement HMI panel needs the recovered legacy project first, because a compiled runtime file is not an editable source.
Expected result of this step: an explicit runtime identity read from the device, and a project archive whose target matches the installed hardware.
Why the option cannot be retrofitted #
Siemens documents the Sm@rt options for panels, Comfort panels and WinCC Runtime Advanced, with a table of HMI devices suitable for use and the number of connections based on the SIMATIC HMI HTTP protocol. Every entry in that table is a device running a WinCC flexible-family runtime. ProTool-based devices are absent, not restricted: the function does not exist in their runtime image.
Licensing works the same way. The WinCC flexible license documentation treats Sm@rtAccess as a runtime option license that unlocks the function in the executing runtime. Buying the engineering package, or even the option license, does not add the function to a ProTool panel; the license has nothing to attach to until a WinCC flexible runtime is running. Acquire the option through Siemens or an authorized distributor when the target device is confirmed, not before.
Configuration lives on the runtime side too: you set the requirements for using the Sm@rt options in the runtime settings editor of the engineering tool, or as an alternative in the Control Panel of the panel itself. Neither location exists on a ProTool device.
The two legitimate paths #
Path 1: migrate the project #
If the installed panel is documented as suitable for WinCC flexible, migrate the ProTool project into the WinCC flexible engineering environment and download the converted project:
- Archive the editable ProTool project and record the PLC connection settings.
- Convert the project with the documented migration route for that source and target.
- Resolve every conversion message: unsupported objects, missing resources and communication differences.
- Compile and download to the target during a controlled window.
- Test local screens, tag values, alarms and operator commands against the controller before touching remote access.
Only after step 5 passes, configure Sm@rtAccess in the runtime settings, set the device network configuration, apply user authentication and permissions, and connect with the supported client. A remote client cannot fix an incorrect PLC address or a dead local connection; verify tags locally first.
Path 2: replace the panel or move to PC runtime #
If the installed hardware cannot run WinCC flexible, the migration path is closed. Select a supported replacement panel and reproduce the PLC connection, screens and installation, or move the application to a PC runtime; what that takes is covered in what running an HMI project runtime on a PC without the panel takes. When the replacement must be a PC-based operator station, choose from industrial panel PCs. Keep the ProTool installation operational until the replacement passes local and remote acceptance testing.
Acceptance checks for the remote session #
Test display access separately from operator control, and define who may issue commands remotely and how local and remote operators coordinate.
| Check | Expected result |
|---|---|
| Local screens, tags, alarms | Values agree with the controller; commands produce the intended response |
| Runtime accepts the option configuration | No option-related diagnostic at startup |
| Client connects | The current application appears and updates, not a stale session |
| Unauthorized user attempts access | Rejected |
| Authorized user operates remotely | Same response as local operation |
Keep remote access on the site's approved industrial network path and restrict it to the required users; never expose the panel directly to the public internet to solve a connection problem. Remote HMI access does not replace machine safety functions.
The decision #
- Panel running a ProTool application: Sm@rtAccess is impossible. Migrate the project to WinCC flexible if the panel supports it, with the option licensed; otherwise replace the panel or move to a PC runtime.
- Panel already running a WinCC flexible-family runtime: license the option, configure it in the runtime settings, and connect with the supported client.
- Either way, the engineering PC is not the gatekeeper. The runtime on the device is.
Questions asked
Can installing WinCC flexible on the engineering PC enable Sm@rtAccess on the existing ProTool panel?
No. The engineering package only builds and downloads projects. The remote-access function lives in the runtime image executing on the panel, and a ProTool runtime image has no Sm@rtAccess service to activate. The panel must receive a WinCC flexible runtime, which means the project must first be migrated.
Where is Sm@rtAccess configured once the panel runs WinCC flexible?
Both set the requirements for using the Sm@rt options on the device; the setting names and connection limits for the exact panel generation come from the documentation for that release.
Does an Ethernet connection to the panel make Sm@rtAccess possible without migrating?
No. A network path carries the remote session, but the session is served by the runtime. A ProTool application has no Sm@rtAccess server inside it, so the connection has nothing to attach to. Migrate the project first, then configure the network and the runtime option.
What if the installed panel cannot run WinCC flexible at all?
Then the migration path is closed and the panel is replaced with a supported target, or the application moves to a PC runtime. Recover the ProTool project first, because the replacement or PC runtime needs the recovered application, and keep the old panel running until the new one passes testing.


