How-to
Running WinCC Runtime Professional V13 on an EC31-RTX IPC
Short answer
Yes: install only the WinCC Runtime Professional component on the EC31-RTX, leave its preinstalled WinLC RTX V4.6 (WinAC RTX 2010) controller untouched, and keep TIA Portal V13 with STEP 7 and WinCC Professional as the only engineering software. Buy a separate runtime license sized in Power Tags, and gate the install on the operating system: the delivered Windows Embedded Standard 2009 image is XP-class while the V13 runtime is released for Windows 7-class and newer systems, so the delivered EC31 hosts the operator interface elsewhere.

On this page
Yes, the split the question implies is the right one: install only the WinCC Runtime Professional component on the EC31-RTX and keep TIA Portal V13 with STEP 7 and WinCC Professional as the only engineering software. The IPC already carries the controller side: it ships as the controller module of the S7-mEC family, preinstalled with Windows Embedded Standard 2009 and WinAC RTX 2010, whose control engine is WinLC RTX V4.6, so no controller software is installed a second time. Two gates decide whether the V13 runtime lands on that box: the operating-system image and a separate runtime license sized in Power Tags. The delivered image is XP-class while the V13 runtime generation is released for Windows 7-class and newer systems, so on a delivered EC31 the operator interface belongs on a released host instead. The sections below cover the component split, the install sequence, the license arithmetic and the per-case decision.
What goes where on this installation #
The roles separate cleanly, and keeping them separate is most of the answer.
| Component | Where it runs | What it does | Your action |
|---|---|---|---|
| TIA Portal V13 with STEP 7 and WinCC Professional | Engineering PC | configures and compiles the software-controller project and the HMI screens, then downloads | nothing to add; no WinAC RTX 2010 installation here |
| WinAC RTX 2010, control engine WinLC RTX V4.6 | EC31-RTX | software S7 controller executing the machine program | leave the factory preinstall untouched |
| WinCC Runtime Professional V13 | EC31-RTX only if its image is on the V13 release list, otherwise another released host | executes the downloaded screens | install the runtime component plus a separate license |
Siemens ships the EC31-RTX with the layers already in place: Windows Embedded Standard 2009 underneath, WinAC RTX 2010 on top of it, WinLC RTX as the control engine. The engineering seat configures; it does not authorize execution — the same boundary as in whether a WinCC Professional entry means the SCADA runtime is installed. The runtime license is the one purchase this split adds, and what a SCADA runtime license covers beyond running the project is exactly why it travels separately from the engineering seat.
Clear the operating-system gate first #
An embedded Windows image carries a selected set of operating-system components, so a matching name does not settle compatibility — the release list for the exact runtime build does. For this pairing the two ends sit a generation apart:
- The EC31-RTX ships with Windows Embedded Standard 2009, an XP-class image.
- WinCC Runtime Professional V13 is released for Windows 7-class and newer operating systems, Windows Embedded Standard 7 included.
- The similar names are the trap: Windows Embedded Standard 2009 and Windows Embedded Standard 7 are different products a generation apart, and the V13 release covers the second while the EC31 ships the first.
The controller side straddles both eras — the WinAC RTX 2010 delivery release highlights Windows 7 support — which is how the same IPC can run the 2010 controller generation while failing the V13 runtime requirement. The EC31 is also reported as phased out since 10/01/2015, so software added here is a legacy addition, not a growth path. The check that settles your own unit: record the installed image and build, the controller version, free storage and RAM, and hold that inventory against the V13 runtime readme. The delivered Windows Embedded Standard 2009 image does not pass, so the delivered case ends at the decision section below; a unit carrying a listed image goes on to the install sequence.
Install sequence on the EC31-RTX #
WinLC RTX is the machine's controller, and installs and restarts on the IPC stop it: commission in a window with the process in a safe state.
- Capture the rollback path first: a full restore image of the IPC's flash disk, copies of the controller and HMI project archives, and the license paperwork in one place.
- Inventory the running unit — installed image and build, controller version (expect WinLC RTX V4.6 under WinAC RTX 2010), free storage and RAM — and hold it against the V13 runtime readme. If the image is not listed, stop at the decision section.
- Size and buy the runtime license before installing; the worked example below shows the arithmetic in Power Tags, and the license is transferred to the IPC.
- Install only the runtime component. Do not repair, update or reinstall WinAC RTX 2010 to make room, and do not install WinAC RTX 2010 on the engineering PC — TIA Portal V13 with STEP 7 and WinCC Professional is the complete engineering set there.
- Restart the IPC and confirm WinLC RTX returns to its running state with no new diagnostics before touching the HMI side.
- In TIA Portal V13, set the HMI device to WinCC Runtime Professional, compile until the project is clean, and download it to the IPC.
- Start the runtime and verify the commissioning screen: a static label plus one live, changing controller value.
Worked example: sizing the runtime license for a 240-tag screen set #
The inputs: the license is the WinCC RT Professional package with 2048 Power Tags that Siemens documents for WinAC RTX and WinCC together on SIMATIC IPCs. The project is an illustrative small machine HMI, not a documented case: 240 external tags — every variable the screens exchange with WinLC RTX — and 95 internal tags used for screen navigation and display formatting.
The rule: a WinCC Runtime Professional license is sized in Power Tags, and Power Tags are the external tags the runtime exchanges with the controller. Internal tags do not count against the license.
The arithmetic: counted load = 240 external tags. Headroom = 2048 − 240 = 1808 Power Tags. A second machine section adds 1920 external tags, so the total is 240 + 1920 = 2160 external tags, and 2160 − 2048 = 112 Power Tags over the package.
The result: the first section fits with 1808 Power Tags of headroom; the two sections together exceed the package by 112 Power Tags.
The decision: within the package capacity the documented license carries the project as it grows; once external tags pass 2048, buy the next larger package before the download, not after a license error at runtime start.
Point the screens at WinLC RTX, not at a Windows host #
The EC31-RTX provides TCP/IP and S7 communication, and the operator interface rides S7 communication over TCP/IP toward the software controller; the PROFINET IO functions serve the I/O side. Configure the HMI connection to the controller endpoint, because the IPC answers at two IPv4 addresses and an address aimed at the wrong one reaches Windows rather than WinLC RTX — the article on why a WinAC RTX IPC responds at two IPv4 addresses sorts out which address serves what.
The first screen proves two different things. Static content proves only that the runtime application starts. Bind one read-only value to a known controller variable with a matching data type and make that value change in the controller; only the changing value proves the connection and the tag mapping. Build the remaining screens on that verified link.
If the operator station gets a touch screen, test input behavior before roll-out: button release events are a known weak spot in WinCC RT Professional, working with a mouse and failing with touch, as the article on the touch release fault in WinCC RT Professional documents.
The decision for each case #
Delivered EC31-RTX, Windows Embedded Standard 2009 image: do not install WinCC Runtime Professional V13 on it. Keep WinLC RTX V4.6 as the controller and host the operator interface where V13 is released — a Comfort Panel configured from the same TIA Portal V13 station and connected to WinLC RTX over S7 communication, or a current industrial panel PC carrying a listed operating system with the V13 runtime and its own license on board.
A unit whose image appears on the V13 release list: run the install sequence — runtime component only, controller untouched, separate license sized in Power Tags.
Either case: treat the EC31 as a legacy platform, keep the restore image, project archives and license records together, and plan the operator interface so it can be re-hosted without re-engineering.
Questions asked
Which BIOS does a first-generation EC31 need for WinAC RTX 2010?
First-generation EC31 controllers with the 2-GB Flash Disk need BIOS version V.2.8.0 or later to run WinAC RTX (F) 2010, per Siemens product information for the EC31. A factory-working unit already meets this; the check matters after servicing, a replacement flash disk or a re-image, when older BIOS can pair with controller software it was never validated against. Confirm the BIOS version before reinstalling controller software on that hardware.
Can the EC31 runtime be updated to V13 SP2 later?
Yes, in the supported order: Siemens publishes updates for WinCC Runtime Professional V13 SP2 that install on the runtime system itself, and they require WinCC Runtime Professional V13 SP2 to be installed there first. So the SP2 runtime goes on before any update package, then the IPC restarts and the screens are re-checked against WinLC RTX. Keep the project and the runtime at matching service-pack levels, as with any TIA Portal HMI.
What communication does the EC31-RTX offer for the HMI and the I/O?
The EC31-RTX works as a PROFINET IO controller supporting RT and IRT, MRP and PROFINET CBA, with TCP/IP as the transport protocol and S7 communication on top, and its configuration reaches up to 32 modules in multiple rows. The I/O traffic rides the PROFINET IO functions; the operator interface connects through S7 communication over TCP/IP, which is the path both a WinCC runtime and a Comfort Panel use toward WinLC RTX.
Should new licenses be bought against an EC31-RTX today?
Treat the EC31-RTX as a legacy addition rather than a growth platform: it is reported as phased out since 10/01/2015, and the current lifecycle entry in Siemens support is the authority on remaining support. If the project does land on one, keep the restore image of the IPC, the project archives and the runtime license records together, so the operator interface can move to a current host without re-engineering when the hardware reaches its end.

