Why multilingual HMI project language configuration needs three parts

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

A multilingual HMI project works only when three parts line up: the project languages are configured, every operator-visible text item has a translated resource, and the runtime language selection reaches those resources with a defined scope. Each failure names the missing part: no change at all, mixed languages, boxes instead of characters, or the old language back after a restart. WinCC OA and WinCC flexible implement the parts differently, so take the configuration path from the documentation matching the installed release.

On this page
  1. What three parts does every multilingual HMI project need?
  2. Where do you find the WinCC OA language configuration steps?
  3. When should the project languages be created?
  4. Why does the language switch leave some screens unchanged?
  5. What decides which language an operator sees after a restart?
  6. Why do translated languages show boxes, corrupted characters or clipped text?
  7. How do you test a multilingual project before commissioning?
  8. Questions asked

A multilingual HMI project rarely fails at translation itself. It fails the way configuration failures always do: the display keeps its old text when the operator picks a language, half the captions switch while the rest stay put, empty boxes appear where characters should be, or everything reverts after a restart. Each of those symptoms points at one of three coordinated parts: the project languages configured in the engineering tool, a translated resource behind every operator-visible text item, and a runtime language selection with a defined scope. This article maps each symptom to the part that is missing and gives the order to configure them in. WinCC OA, WinCC flexible and classic WinCC implement the parts differently, so the exact settings come from the documentation matching the installed release.

What three parts does every multilingual HMI project need? #

Every multilingual HMI project stands on three coordinated parts: the project languages configured in the engineering tool, a translated resource behind every operator-visible text item in each of those languages, and a runtime language selection that reaches those resources with a defined scope. A resource is a stored text item — a caption, a tooltip, an alarm text — that the runtime retrieves through a language-aware lookup, instead of the words being typed into the object or buried in a script.

Remove one part and the failure is predictable. With no configured languages there is nothing to select. With missing translations the runtime shows fallback or untranslated text. With no working selection path the operator's choice never reaches the screen. The split is product-independent — it fits a small operator panel and a distributed PC system alike — while each product stores and connects the parts in its own way.

Where do you find the WinCC OA language configuration steps? #

Take the WinCC OA language steps from the documentation that matches the installed release, because WinCC OA implements language handling differently from WinCC flexible and habits carried over from flexible projects do not transfer. Record the exact release from the installed software first, then open the help or official documentation for that release and locate two things: where the project languages are configured, and how the runtime selects the operator language.

A product brochure describes capability, not configuration, and cannot stand in for the manual. The rule cuts both ways: the Text Library workflow documented for classic WinCC V7.x belongs to that product line and should not be assumed for WinCC OA either. What transfers is the checklist — languages, resources, selection — verified item by item against the OA documentation for your release.

When should the project languages be created? #

Create every language the project will use before the runtime first starts, and build the screens in one working language: the documented WinCC V7.5 runtime-language example creates the languages in the WinCC Text Library before starting runtime, because a runtime that starts without a language cannot display it. The WinCC V7.4 documentation completes the order: configure the project in the preferred language and hand over the text for translation once the project is complete. Translating while screens are still changing means translating the same strings twice, so freeze the source text screen by screen, then translate.

If a language is added to an existing project later, plan a runtime restart so it is loaded. The project-language setup and runtime switching for classic WinCC are walked through in a guide to configuring multilingual WinCC applications, which serves as a useful reference even when the target is a different product.

Why does the language switch leave some screens unchanged? #

When nothing at all changes, the selection is not reaching the display resources; when some captions switch and others stay put, the untouched ones are fixed literal text typed directly into objects instead of translatable resources. Literal text bypasses the language lookup — no selection mechanism can translate it, because there is nothing stored to look up. Move those captions into the project's translatable text mechanism, the one the release documentation names, and the switch starts reaching them.

Screens that are already open when the language changes follow the documented refresh behavior: some runtimes update open panels at once, others apply the new language the next time a screen opens. Confirm which behavior the installed release documents, then lay out navigation so an operator is never left reading a mixture of two languages on one panel.

What decides which language an operator sees after a restart? #

Three settings decide it: the selection mechanism the runtime exposes to the operator, the scope that the selection applies to, and the fallback language the project returns to when a translation is missing or the station restarts. Scope is the part of the application a change touches. A project-wide switch moves every connected display to one language at once; a per-station or per-session scope lets different operators run different languages at the same time. Confirm which scope the installed release documents before promising the second.

The fallback language needs a deliberate decision, because it is what the station shows after every restart unless the runtime persists the last selection — a common field complaint is a terminal that reverts to the engineering language each morning. Set the fallback to the language the operators at that station actually need, then prove the restart behavior in the acceptance test instead of assuming it.

Why do translated languages show boxes, corrupted characters or clipped text? #

Boxes and corrupted characters are a font fault, not a translation fault: the active font does not contain the script, so choose a font with coverage for every configured language before blaming the resource files. A Latin-only font renders Chinese, Korean, Cyrillic or Arabic as empty boxes no matter how correct the translation behind it is. A Comfort Panel showing boxes instead of Korean is exactly this failure, covered in why Korean text fails to display on a Comfort Panel. The list of fonts a panel project offers can itself be the restriction, as explained in why WinCC flexible shows only Tahoma in a panel project. Mixing Chinese and Western languages in one WinCC runtime brings its own font and encoding settings, covered in a guide to configuring the WinCC V7.0 runtime for Chinese and Western languages.

Clipping is a separate fault: translated text routinely runs longer than its source, so leave length reserve in buttons, labels and column widths, and check the layout against the longest language, not the shortest.

How do you test a multilingual project before commissioning? #

Test the deployed runtime, not the engineering preview: select every configured language, navigate the representative screens, check every text category, then restart the station and confirm the startup language, signing off a matrix of languages against text categories. Size the matrix from what the project contains. Worked example with illustrative numbers: a project configured with 4 languages and an inventory of 800 translatable text items carries 4 × 800 = 3,200 translated strings; with the four test categories — captions, messages, dynamic values and navigation — the sign-off matrix is 4 languages × 4 categories = 16 cells, each recorded pass or fail on the target hardware. A screen that mixes two languages fails even when every word on it is readable.

After the matrix, restart the station and record which language comes back; that reading must match the fallback decision. Do the first configuration pass in a recoverable copy of the project and run the language tests on a bench system, never on the station that controls a live machine.

The matrix hands you the decision for each failure:

  • Nothing changes on selection: connect the runtime selection to the display resources.
  • Some captions never switch: convert that literal text into translatable resources.
  • A language is missing after it was added: create it before runtime start, then restart the runtime.
  • Boxes instead of characters: change to a font that covers the script.
  • The old language returns after a restart: set the fallback language to what that station's operators need.

Questions asked

Does the language of the engineering software change what the operator sees?

No. The tool language belongs to the engineer's interface only. Operators see the languages configured as project languages with resources behind them, whatever language the project was built in. Set the engineering tool to the language you work fastest in; it has no effect on the text the runtime displays.

Should tag names and equipment identifiers be translated?

No. Keep tag references, communication addresses and equipment identifiers exactly as built, and translate only the operator-facing captions and descriptions. Scripts, alarm definitions, archives and drivers all reference those names, so renaming an identifier to force a translated display breaks references without improving localization.

How should scripts that assemble text from several pieces be handled?

Store complete sentences per language and insert the variable values separately. Fragments translated one at a time produce wrong word order in languages that arrange sentences differently, and a number or date formatted for one locale can be misread in another. Complete stored messages keep the grammar correct in every configured language.

Can two operators use different languages at the same time?

Only with a per-station or per-session selection scope. Where the switch is project-wide, give each language group its own runtime instance or operator station instead of sharing one, and confirm the documented scope for the installed release before promising two languages on one system.

Is a readable fallback language proof the translation is complete?

No. A fallback keeps the screen readable while hiding gaps: every missing translation quietly shows the fallback text, so the display looks finished. Completeness is proven only by the language matrix on the target runtime, category by category. A project that reads perfectly in its fallback language can still be missing most of its translations.

Keep reading

  • Explainer

    Which runtime languages WinCC V7.5 supports and which need the dongle

    WinCC V7.5 supports any runtime language the PC's operating system supports, so English and Russian need only OS language support and suitable fonts. Simplified Chinese, Traditional Chinese, Korean and Japanese additionally require the ASIA hardware dongle included with the WinCC Asia versions. You create runtime languages in the WinCC Text Library, following the multilingual-project procedure in Working with WinCC, sections 14.1 and 14.2.4, which also applies in V7.5 SP2.

    HMI and touchscreens

  • Checklist

    What a spare HMI PC needs before the old runtime PC fails

    Build the spare without a license: install the same runtime version on the same operating system as the working PC, restore the application by the product's documented method rather than a copied folder, and when the old disk fails, recover the license through the vendor's documented process. First confirm whether the runtime is WinCC or InTouch, because the two are not interchangeable. A spare that must run alongside the original needs its own runtime license.

    HMI and touchscreens

  • How-to

    Deploying a compiled WinCC Runtime Advanced project to a separate PC

    Compiling a WinCC Advanced HMI in TIA Portal V14 generates the runtime file in the project's HMI subdirectory. Copy that file to the target PC — which needs WinCC Runtime Advanced installed and a matching runtime license, but no TIA Portal — and open it to start runtime, or download the HMI station directly over a configured transfer connection.

    HMI and touchscreens

Why an HMI touch foil is not a field-replaceable part