Why the WinCC RT Advanced button stays inactive in TIA Portal
Short answer
The RT button only starts a WinCC RT Advanced station that exists in the project and is selected. With a Comfort Panel selected it stays inactive, and a runtime component installed on the PC does not change that. Test the panel with the simulation button to its left; add a WinCC RT Advanced station when the application must run on a PC.

On this page
- What the RT button applies to
- Why installing a runtime component does not activate it
- Adding and selecting a WinCC RT Advanced station
- Testing a Comfort Panel project with simulation
- Worked example: a project with one Comfort Panel and no RT Advanced station
- Deploying a WinCC RT Advanced application to a PC
- The decision for each case
- Questions asked
The RT button is inactive because of what is selected in the project tree, not because software is missing. In TIA Portal that button starts the runtime of the selected station, and it applies only to a WinCC RT Advanced station; when the project tree shows a Comfort Panel as the only HMI device, TIA Portal has nothing the action applies to and keeps it greyed out. Installing a runtime-start component on the PC cannot change that, because the button reads the project target and the current selection, never the installed software list. Test the panel project with the simulation button to the left of the RT button, which runs almost every project function and can connect to PLCSIM or a real controller. Add a WinCC RT Advanced station only when the application is genuinely meant to run on a PC, then load it through the Runtime Loader.
What the RT button applies to #
TIA Portal decides its toolbar actions from two inputs: the target each project object is configured for, and the object selected at this moment. A target is the device or runtime platform an HMI application is built for. A Comfort Panel application and a WinCC RT Advanced application are different targets even though both give you operator screens and access to PLC data, and each target owns its own launch action.
The rule for the button in question is short: it activates when a WinCC RT Advanced station exists in the project and that station is the selected object. Selecting a panel never activates it. The same target-and-selection logic decides the other PC runtimes too, and the walkthrough on selecting a WinCC Unified PC target in TIA Portal shows the same decision made for a different runtime.
Read the configured device type in the project tree before touching the toolbar. A Comfort Panel branch with an inactive RT button is the tool behaving correctly, not a fault to repair. That one reading tells you which of the paths later in this article applies to your project.
Why installing a runtime component does not activate it #
The installed software and the project target answer different questions: the project defines what gets generated, and the installed software executes the result. A button that starts the runtime of the selected station cannot be switched on from the Windows installed-software list, so no installation on the engineering PC will activate it while a panel is selected. That is why the runtime-start component changed nothing.
Check what was actually installed before assuming the runtime is present. An entry such as WinccRP, described as a runtime start component, is a launcher rather than the runtime platform, and the two are not interchangeable. Read the full product name in the installed software list and confirm the complete WinCC RT Advanced product is on the PC that will run the application. A missing runtime explains a PC that cannot execute the generated application later; it never explains the inactive button, which the selection alone governs.
Adding and selecting a WinCC RT Advanced station #
When the application belongs on a PC, create the station the action expects:
- In the project tree, run the Add new device command and pick the WinCC Runtime Advanced entry from the device tree the dialog opens.
- Select the new WinCC RT Advanced station in the project tree. The RT button becomes active for that selection straight away, which confirms the target was the whole problem.
- In the device view, take the IE General communication module from the hardware catalog and add it to the PC station, so the station has an interface on which the Ethernet connection to the controller can be configured.
- Remember that the station in the project is only configuration. The PC that will run the application needs the full WinCC RT Advanced product installed, with its release matched to what the project expects.
If the station exists and is selected but the button is still inactive, recheck the selected object and the configured target before reinstalling anything. Those two readings separate a selection problem from an installation problem.
Testing a Comfort Panel project with simulation #
For a panel target, the simulation button to the left of the RT button is the intended path, and it covers more than its size suggests. Simulation executes the HMI application on the engineering computer, so almost every project function can be checked without deploying anything to the panel. It works without the Tag Simulator, and it can connect either to PLCSIM or to the real controller. For a Comfort Panel project that has to reach a simulated S7-300, the article on connecting a Comfort Panel to a PLCSIM S7-300 with NetToPLCSim gives the bridge setup.
A simulation that opens proves the project executes; it does not prove communication. Open a screen with a known PLC-connected value and change that value at the controller: if the controller value moves and the HMI follows, the connection and the tag mapping work; if the screen opens but the value never moves, correct the connection configuration instead of chasing the toolbar.
One caution when the simulation talks to a real controller: a command on a test screen can drive a real output, so watch read-only values first and exercise writes only under an authorized machine test condition.
Worked example: a project with one Comfort Panel and no RT Advanced station #
The case this article opened with, with the inputs made explicit:
- HMI devices in the project: 1 Comfort Panel, read from the project tree.
- WinCC RT Advanced stations in the project: 0.
- Selected object: the Comfort Panel.
- Installed on the engineering PC: 1 runtime-start utility, an entry such as WinccRP; whether the full runtime product is installed is unconfirmed.
The rule in words: the RT button activates only when the project contains a WinCC RT Advanced station and that station is the selected object. Panels are excluded from the action, and the installed software list is not an input.
The arithmetic:
- Total HMI devices: 1 panel + 0 RT Advanced stations = 1.
- Stations eligible for the RT action: 1 total minus 1 panel = 0 eligible stations.
- Button active requires at least 1 eligible station and that station selected: with 0 eligible stations both conditions fail, so the button is inactive for every possible selection.
- Contribution of the installed software list to the button's state: 0, despite the 1 runtime-start utility on the PC.
Result: the button stays inactive no matter what is selected, which matches the observed symptom, while the simulation action applies to the panel and runs, which is why the panel simulation worked while the RT button refused to.
Decision: with 0 eligible stations, either the panel is the intended target and you simulate, or the target is a PC and you add the station. The button turns active the moment a WinCC RT Advanced station exists and is selected; nothing about the installed software has to change first.
Deploying a WinCC RT Advanced application to a PC #
A PC application reaches its machine differently from the way a project reaches a panel: a panel takes a download, a PC runtime takes the generated output. Generate the application for the WinCC RT Advanced station first and resolve every reported error, then load the generated runtime files through the Runtime Loader or copy them manually, following the deployment instructions for the installed release. Point the loader at the files generated for the intended station, not at an older application left on the machine.
When this runtime is to become the operator interface at the machine rather than a test on your desk, it needs hardware built for that spot, and industrial panel PCs give the runtime a touchscreen and a housing meant for a cabinet door or a wall. Before commissioning, count the tags the application exchanges and check them against the runtime tag license tiers for an HMI panel PC, because the tag count decides the tier.
Version matching has its own rules on the PC side. If the project came from an older TIA Portal release, check the version conditions before generating; the article on running a TIA Portal V14 HMI on WinCC Runtime Advanced works through one version combination end to end.
The decision for each case #
- The application belongs on the panel, or you are still engineering it: keep the panel target and use the simulation button. The inactive RT button is correct behavior; do not create a PC runtime station just to light a toolbar button.
- The application must run on a PC: add the WinCC RT Advanced station with the Add new device command, select it, confirm the full runtime product is installed on the target PC, add the IE General module, configure the connection, generate, and load the generated runtime files through the Runtime Loader.
- The button is active but the runtime misbehaves: the project side is done, so record the engineering release, the configured target, the selected object and any diagnostic message, and compare the installed runtime release against the project's requirements before deploying.
In every one of these cases the button's state was never the problem to solve; the target was. Decide where the application will really run, and the correct launch action follows from that decision.
Questions asked
Can a TIA Portal project contain a Comfort Panel and a WinCC RT Advanced station at the same time?
Yes. A project can hold several HMI devices side by side, which is common during a migration when the same screens move from a panel to a PC runtime. Each device keeps its own target and its own connection settings. The toolbar actions follow your selection, so with both stations present you select the panel to work on the panel target and select the WinCC RT Advanced station to work on the PC runtime.
How do I add the communication driver for an RT Advanced connection?
Open the Connections editor of the HMI device, double-click the add row in the connection list, then pick the driver for your controller in the Communication driver column. This editor is the same one a Comfort Panel project uses, so the steps you followed for the panel connection are the same ones for the PC station.
Why does the IE General module matter for a PC station?
A PC station in the project is a software frame, so it has no port of its own for the network cable. The IE General communication module gives that station an Industrial Ethernet interface, and the connection to the controller is then configured on the interface the module inserts. Without it there is no interface to assign and the Ethernet connection cannot be completed.
The RT button is now active but runtime still does not start. What should I check next?
The project side is finished, so the remaining checks are on the target PC: confirm the full WinCC RT Advanced product is installed there rather than only a runtime-start utility, and confirm its release matches what the project expects. Then load the generated runtime files through the Runtime Loader or copy them manually, and point the loader at the application generated for this station rather than an older one.
Is simulation enough before I commission a panel project?
Simulation proves that the screens, scripts and controller communication behave as configured, because it can run against PLCSIM or the real controller. It runs on the engineering computer, so it does not exercise the panel itself: the device's own runtime, its font handling and the download are confirmed on the real hardware. Treat a clean simulation as the gate that says the project is ready for transfer, not as the final test.