Troubleshooting
Backing up an MP277 by MPI when WinAC MP 2008 will not install
Short answer
Take the backup with ProSave over Ethernet from the Windows 10 PC: it needs no WinAC MP package, no PCS7 and no MPI adapter. The MPI route fails there because WinAC MP 2008 v4.1.1 runs only on Windows XP SP3 and the adapter's USB passthrough freezes an XP virtual machine, so MPI programming moves to a physical XP machine with the PC Adapter set to 187.5 kbps.

On this page
- Why the MPI upload fails on Windows 7 and Windows 10
- Why the XP virtual machine freezes at the adapter
- The ProSave backup over Ethernet
- MPI programming from a physical Windows XP machine
- The arithmetic that picks Ethernet for the backup
- If the upload still reports an unrecognized device
- What the backup restores, and what it does not
- The decision
- Questions asked
Your backup does not need MPI at all. ProSave over the Ethernet connection that already works copies a complete backup — project, panel image and settings — from the MP277 to your Windows 10 PC, and it runs there without WinAC MP, without PCS7 and without an MPI adapter. The MPI route is closed on that PC for two reasons you cannot engineer around: WinAC MP 2008 v4.1.1 runs only on Windows XP, so PCS7 v9.0 on Windows 10 can never register a SIMATIC HMI Station, and handing the MPI/PROFIBUS USB adapter to an XP virtual machine freezes that machine as soon as the adapter enumerates. Take every backup over Ethernet, and program over MPI from a physical Windows XP machine.
Why the MPI upload fails on Windows 7 and Windows 10 #
WinAC MP 2008 is the Multi Panel option that registers the SIMATIC HMI Station: Siemens files it under Multi Panel Options (support entry 42201149), and you build a WinAC MP project with its system library (entry 26729818). Siemens answers the operating-system question directly — the package is executable only under Windows XP, not Windows 7 (entry 42713116) — and Windows 10 is out for the same reason: no release exists for either system, so v4.1.1 is the end of the line. No PCS7 version changes this, because the wall is the operating system, not the engineering tool.
That is why the upload on your Windows 10 PC finds the panel's node and then reports the device as not recognized: nothing installed there can match the panel to a known device. The message is a registration failure, not a password, cable or bus-rate failure, and it will not clear until the upload runs on an XP installation. The same limits apply to the MP177 and MP377 Multi Panels.
Why the XP virtual machine freezes at the adapter #
On the Windows 10 host the adapter enumerates and works; the freeze starts when the XP guest claims it over USB passthrough, and it appears with the network set to NAT and set to bridged alike — that setting cannot matter, because the failing path is USB, not Ethernet. The deeper behavior of these adapters under a hypervisor is covered in why MPI works but PROFIBUS does not in a STEP 7 VM; the decision here is short. Stop spending time on passthrough and put Windows XP on physical hardware — an old laptop or an industrial PC with a USB port is enough.
The ProSave backup over Ethernet #
ProSave makes a complete backup directly from the panel, including the configuration (Siemens support entry 28928853), and the package installs on the Windows 10 PC with no PCS7 and no WinAC MP. The sequence:
- On the panel, open Control Panel, then Transfer, note the Ethernet address and leave transfer enabled.
- Put the PC on the same subnet and ping the panel; the S7 connection runs over TCP port 102, so anything between the two ends has to pass it.
- In ProSave, select the MP277 device type, set the connection to Ethernet with that address, and connect.
- Run the backup, save the image file, record its size, and copy it off the PC.
The screens are the same as in backing up a KTP600 Basic Mono PN with ProSave over Ethernet; only the device type and address change. One caution before you switch the panel to transfer: transfer mode takes the panel's runtime offline, so take the backup on a stopped machine or in a planned window.
MPI programming from a physical Windows XP machine #
Put Windows XP SP3 on real hardware and install WinCC flexible 2008 with the image versions the panels run. Add WinAC MP 2008 only where the panels sit as SIMATIC HMI Stations inside a PCS7 project; a standalone WinCC flexible upload does not need it. Connect the PC Adapter USB A2 (6ES7 972-0CB20-0XA0), open Set PG/PC Interface, and set:
- Access point S7ONLINE, assigned to PC Adapter (MPI).
- Transmission rate 187.5 kbps, the value that must match the panel's MPI setting.
- Adapter MPI address 0; the panel keeps its own configured address.
The same access-point assignment is what lets a PC Adapter USB A2 serve as the WinCC runtime MPI channel. From this machine, MPI-wired panels are backed up and programmed over the same adapter, and Ethernet panels upload from here too.
The arithmetic that picks Ethernet for the backup #
Take a 30 MB backup image as an example size. Over MPI the bus rate is 187.5 kbps, so the raw transfer time is 30 MB × 8 = 240 Mbit, then 240 Mbit ÷ 0.1875 Mbit/s = 1280 s, about 21 minutes — before frame overhead, gaps and retries, which only add time. Over a 100 Mbit/s Ethernet link the same 240 Mbit takes 240 Mbit ÷ 100 Mbit/s = 2.4 s raw. That is a ratio of more than 500 to 1, and it holds whatever the real image size. Any panel with an Ethernet port is backed up over Ethernet; MPI is for panels wired without one, and for programming.
If the upload still reports an unrecognized device #
- Confirm which system you are on: the upload has to run on the XP installation. On Windows 7 or Windows 10 the same message is expected, and no setting clears it there.
- Read the node list before anything else. A visible panel node means the adapter, cabling and rate are fine and the failure is the software registration; a missing node points instead at rate, addressing or bus termination.
- Give every node its own MPI address: a duplicate knocks both nodes off the bus, and the adapter keeps the address set above.
- If the selection lists no device to transfer to an MP277 at all, that is a separate fault, covered in WinCC flexible 2008 SP2 lists no device to transfer to an MP277.
What the backup restores, and what it does not #
A ProSave backup restores the same panel type: an MP277 image does not go onto an MP377 even with the same display size, so a different spare means re-creating the project on it. A restore that also updates the panel image can fail with a memory message, the failure covered in MP277 OS update fails with not enough memory on destination device. And an image is not source: the editable project comes back only through a WinCC flexible upload from the XP machine, the same distinction as in OP270 upload: ProSave backup versus WinCC flexible backtransfer.
The decision #
- The panel has Ethernet and you need a backup: ProSave over Ethernet from the Windows 10 PC. Do it today.
- You need the editable project: the physical XP machine, WinCC flexible 2008 plus WinAC MP 2008 where PCS7 integration is involved, and the upload over Ethernet or MPI.
- The panel is wired for MPI only: the same XP machine, PC Adapter USB A2 at the panel's rate, backup and programming over MPI.
- The virtual machine: retired from this job. The freeze sits on the USB enumeration path, no virtual setting reaches it, and XP on real hardware ends the problem.
Questions asked
Can I install WinAC MP 2008 on Windows 7 or Windows 10 with compatibility mode?
No. Compatibility options change the installer environment, but the package is built to execute only on Windows XP, so on a newer system the SIMATIC HMI Station registration never happens and the upload still reports an unrecognized device. A newer PCS7 version does not help either. A physical machine running Windows XP is the supported route.
Does the freeze mean my virtual machine is misconfigured?
No. The guest was verified as correctly configured, and the same adapter works on the host, so memory, drivers and network mode are all fine. The failure arrives with the USB handover itself, at enumeration, and it takes the whole virtual machine down. That is why the fix is physical hardware rather than another round of virtual machine settings.
Is the unrecognized-device message caused by password protection on the panel?
No. The message appears at device recognition, before any password or transfer check runs, and the panels in this situation are not locked. Knowledge protection would prompt at a later step instead. The cause is the missing software registration on the uploading PC, and the fix is running the upload from the XP installation.
Which MPI addresses should the panel and the PLC use?
Keep every node at its own address: the adapter stays at 0, and in most plants the panel sits at 1 and the CPU at 2. Addresses are read and changed in the panel's communication settings. A duplicate address knocks both nodes off the bus, and the adapter must never share the panel's address.